Car Parking Smoke ventilation fan calculation:
1.Total Car parking Area
2.Floor Height.
3.Type of Ventilation system used (For more Detail)
*Ducted Ventilation system
*Impulsive Ventilation system
*Induction ventilation system
Here I considered Ducted Ventilation System
Total Car Parking Area - 675 m2
Floor Height - 4 m`
Volume of the building = Area * Height
= 675*4
= 2700 m3
Click here to visit our site
Formula:
Air Changes Per Hour = (Volume /60 )*ACH
1. In Case of Normal Mode
Exhaust fan at Normal Mode shall operate @ 6 ACH Exhaust
Space volume = 2700 m3
For 1 ACH =(2700*1000/60x60)
=750 L/s
For 6 ACH =750*6
=4500 L/s
So, Required Exhaust Fan Capacity @ normal mode = 4500 L/s
2. In Case of Fire Mode
Exhaust fan at Fire Mode shall operate @ 10 ACH Exhaust
Space volume = 2700 m3
For 1 ACH = 750 m3
For 10 ACH = 750*10
= 7500 L/s
So, Required Exhaust Fan Capacity @ normal mode = 7500 L/s
Fresh Air fan Capacity is 85% of Exhaust Fan Capacity
Then, Required Fresh Air Fan Capacity @ normal mode = 4500*85%
=3825 L/s.
Fresh Air Fan Capacity @ Fire mode = 7500*85%
= 6375 L/s
Click here to visit our site
Calculation Summary:
Fresh Air Fan capacity @ Normal Mode = 3825 L/s
Fresh Air Fan capacity @ Fire Mode = 6375 L/s
Exhaust Fan capacity @ Normal Mode = 4500 L/s
Exhaust Fan capacity @ Fire Mode = 7500 L/s
Note :
Air Change per hour @ normal mode & fire mode May differ based on their country standard norms